HVDC & VSC Converter Valve Capacitors

Application · HVDC and VSC converter valves

In an HVDC or VSC station, the highest-voltage capacitor positions are valve grading, thyristor snubber, RC dividers and DC filter damping. HVC supplies these as screw-terminal ceramic discs from 10 kV to 150 kV, 100 pF to 30,000 pF, N4700 Class I dielectric, screened to partial discharge ≤ 5 pC at rated voltage.

High voltage direct current transmission moves bulk power over distances and submarine routes where AC cannot compete. Whether the converter uses line-commutated thyristors (LCC) or voltage-source IGBT modules (VSC, including MMC), the valve needs capacitors that hold a defined value under DC stress, pass partial-discharge screening, and survive decades of thermal cycling.

This page is written for three buyers outside the original valve OEM: engineers qualifying a seconda fonte for an existing design, maintenance teams sourcing replacement spares for installed valves, and manufacturers of impulse and partial-discharge test equipment.

HVC screw-terminal doorknob capacitor, 40 kV N4700, M5 stud

Screw-terminal doorknob capacitor, 40 kV / 2000 pF, N4700, M5 stud.

What the valve position actually specifies

  • Rated DC voltage 10 kV to 150 kV, capacitance 100 pF to 30,000 pF
  • N4700 Class I dielectric, −40 °C to +125 °C, 10,000 MΩ insulation resistance
  • Partial discharge screened to ≤ 5 pC at rated voltage, unit by unit
  • Hi-pot at 150%–200% of rated voltage before shipment
  • Single or double disc, stud M4 / M5 / 8-32 UNC, built to drawing

Gamma completa: screw-terminal doorknob capacitors, 203 catalogue models.

Where capacitors sit in an HVDC or VSC converter station

Each position has its own voltage class, capacitance band and failure consequence. The table below maps the six positions that appear in a converter station to the component family that serves them.

PosizioneTensione tipicaFunzioneFamiglia di componenti
Valve grading (thyristor levels)10–100 kVDivides DC and impulse stress evenly across series-connected devicesScrew-terminal ceramic disc, N4700
Thyristor RC snubber10–100 kVLimits dv/dt and reverse-recovery overshoot at turn-offScrew-terminal ceramic disc, N4700
RC or capacitive divider10–150 kVReference for voltage measurement and protectionScrew-terminal ceramic + resistore a film spesso
DC filter damping10–50 kVDamps resonance in DC-side filter banksScrew-terminal ceramic disc
Gate-drive and auxiliary supplies0.7–3 kVSnubber and DC-link support in the low-voltage electronicsMetallized polypropylene film (DTS)
MMC submodule DC link2–6 kV, millifaradEnergy buffer per submoduleNot supplied by HVC

Why Class I ceramic is specified at valve level

A valve grading or snubber capacitor is selected on what it does at rated DC voltage, not on its catalogue capacitance. Four parameters decide whether a part survives in a valve hall.

Voltage classes and capacitance ranges supplied

Screw-terminal ceramic discs, N4700 / Y5T / Y5V, single or double disc, M4 / M5 / 8-32 UNC stud.

tensione nominaleGamma di capacità
10 kV DC560 pF – 20,000 pF
15 kV DC250 pF – 10,000 pF
20 kV DC200 pF – 10,000 pF
30 kV DC190 pF – 5,900 pF
40 kV DC100 pF – 15,000 pF
50 kV DC100 pF – 8,000 pF
60 kV DC500 pF – 4,000 pF
70 kV DC10,000 pF
80 kV DC2,000 pF – 5,000 pF
100 kV DC500 pF – 3,000 pF
120 kV DC1,000 pF
150 kV DC800 pF

Values above the listed band, non-standard stud threads and double-disc stacks are built to drawing. Send the voltage, capacitance, tolerance, body envelope and stud specification.

Representative part numbers

One part per voltage class, each linking to its specification page. The catalogue covers 203 doorknob models; values outside the bands above are built to drawing.

Cod. produttore:TensioneCapacitàDielettricoBody / stud
HVCT8G-10KV-DL30-561K10 kV560 pFN4700D30 × H15, M4
HVCT8G-20KV-DL30-201K20 kV200 pFN4700D30 × H17, M4
HVCT8G-30KV-DL50-222K30 kV2200 pFN4700D50 × H20, M4
HVCT8G-40KV-DL55-202K40 kV2000 pFN4700D55 × H25, M5
HVCT8G-50KV-DL80-502M50 kV5000 pFN4700D80 × H75, M5
HVCT8G-100KV-DL60-501K100 kV500 pFN4700D60 × H39, M5

Tolerance K (±10%) or M (±20%); other tolerances on request. Every part is quoted with its partial-discharge test record.

Percorso di qualificazione

Converter valve programmes normally run the candidate part through four stages before it enters the approved list. HVC supports each stage with documentation:

StageWhat the customer measuresWhat HVC supplies
1. Datasheet reviewVoltage, capacitance, tolerance, body size, studDatasheet with drawing and part-number decoding
2. Incoming sample testCapacitance, DF, IR, hi-pot, partial dischargePD screening data and hi-pot records
3. Environmental qualificationTemperature cycling, damp heat, long-term voltage1000-hour life test reports
4. Qualifica del fornitoreISO 9001 QMS, traceability, change notificationISO 9001:2015 certificate, batch traceability

Most converter programmes start under NDA because the specification discloses valve topology and operating margins. HVC signs customer NDAs and works under them for drawing-level data exchange.

Film capacitors for auxiliary circuits

The low-voltage electronics around the valve, including gate-drive supplies and IGBT snubbers in auxiliary converters, take metallized polypropylene film rather than ceramic. The HVC DTS series covers 700–3000 Vdc, 0.0068–5.6 µF, self-healing polypropylene metallized film, in six voltage classes. View the film capacitor range.

Replacement spares for installed valves

Installed converter valves stay in service for decades while the original capacitor supplier changes ownership, discontinues the body size, or moves the part to a different plant. The valve position still needs a part with the same body envelope, stud thread and capacitance, because the grading ratio and the mechanical fit are fixed by the existing hardware.

HVC builds to the original drawing and supplies a cross-reference table with the offer. Send the original part number, the drawing or the datasheet page, the annual spare quantity and the required acceptance test. For retrofit campaigns we quote matched sets so a single valve level is replaced from one production batch.

Capacitors for impulse and partial-discharge test equipment

Impulse voltage generators, DC hipot sets and partial-discharge test benches load their capacitors very differently from a converter valve: short, high-current pulses at low repetition rate, followed by long idle periods. The selection criteria are peak current, stored energy per shot and mechanical mounting, not continuous ripple current.

Test-set positionCiò che sottolineaSpecifiche da confermare
Impulse generator stage capacitorPeak discharge current, mechanical shockCapacitance, rated DC, stud and body, PD at rated voltage
DC hipot dividerLong-term DC stress, leakage stabilityInsulation resistance, capacitance stability over temperature
PD test coupling capacitorBackground noise floorPD level at rated voltage, low loss, stable capacitance

For laboratory and university benches the same parts serve Marx generators, capacitor banks and pulsed-power experiments. Single-unit and small-lot orders are accepted because the requirement is usually one specific voltage and capacitance.

Domande frequenti

What voltage class do HVDC valve grading capacitors use?

Valve grading and snubber positions in LCC valves typically sit in the 10–100 kV band, with dividers reaching 150 kV. HVC covers 10 kV to 150 kV in screw-terminal ceramic disc form.

Why does partial discharge matter more than capacitance tolerance here?

Because a discharge inside the dielectric grows under DC stress while the capacitance reading stays in tolerance. Screening every unit to ≤ 5 pC at rated voltage removes the parts that would fail in service; capacitance tolerance alone does not.

Can a Class II disc replace a Class I part in a valve?

Not for grading or snubber duty. Class II dielectrics lose capacitance with DC bias, temperature and age, which changes the grading ratio across the thyristor string. N4700 Class I holds its value over −40 °C to +125 °C.

What capacitance is available at 40 kV?

100 pF to 15,000 pF in standard bodies, with larger values built to drawing. 40 kV is the most widely specified class in the HVC screw-terminal range.

Do you work under NDA?

Yes. Converter and defence programmes normally start with a mutual NDA before drawings and operating margins are exchanged.

Can you match a discontinued Murata or TDK screw-terminal part?

Yes, when the original drawing or datasheet is available. HVC supplies the cross-reference table and the replacement part number with the quotation.

Can you supply spares for a valve that is already in service?

Yes. Send the original part number or drawing and the annual spare quantity. We quote matched sets so one valve level is replaced from a single production batch, with the partial-discharge record per unit.

Do you supply capacitors for impulse generators and PD test sets?

Yes. Single units and small lots are accepted. Tell us the stage voltage, capacitance, peak discharge current and mounting, and we return the part number with the PD and hi-pot test data.

Sending a valve capacitor requirement?

Send the voltage class, capacitance, tolerance, body envelope, stud and annual quantity. HVC replies with a matching part number, partial-discharge screening data and a 1000-hour life report. NDA on request.

Richiedi un preventivo tecnico →